- Thermal comfort according to EN ISO 7730, SIA 382/1
- Building material class A2-s1, d0 according to EN 13501-1
- Very high heating and cooling capacity
- With optional acoustic inlay: superior sound absorption values (class A)
- Combination of high thermal capacity and individual ceiling design
- Easy to install
- Anodised profiles available
- Components can be integrated
- Can be combined with ARCHISONIC®
|
Cooling capacity
> 150 W/m² (8 K) |
|
|
Heating capacity
> 150 W/m² (15 K) |
|
|
Sound absorption
Class A |
|
|
Carbon footprint
< 75 kg CO2/m² |
|
Cooling capacity
The cooling capacity corresponds to the amount of energy per second removed from the room via heat radiation and convection. It is determined in accredited climate laboratories in accordance with SN EN 14240.
For comparison: the heat emitted by a person in an office via radiation and convection is approx. 70 – 80 W; the heat emitted by a laptop is approx. 20 – 50 W.
Heating capacity
The heating capacity corresponds to the energy per second added to the room via heat radiation and convection. It is determined in accredited climate laboratories in accordance with SN EN 14037.
For comparison: The heat output of a person in an office via radiation and convection is approx. 70 – 80 W, whilst that of a laptop is approx. 20 – 50 W.
Sound absorption
As the largest unobstructed surface in a room, the ceiling is particularly well suited to sound absorption. The sound absorption class is determined in accordance with EN ISO 11654, based on measurements carried out in accordance with EN ISO 354 in accredited laboratories.
It serves as a parameter for acoustic designers to calculate the effect of a product on a room’s reverberation time.
Carbon footprint
open
Convection
visible
Cooling (EN 14240:2004):
- up to 241 w/m² (8 K)
Heating (EN 14037:2016):
- up to 303 w/m² (15 K)
With sound absorber αw: up to 0,90 (L)
Sound absorption class A
(EN ISO 11654)
Thermal comfort according to
EN ISO 7730, SIA 382/1