V51/NS
Pressure Reduction Box

Designed for applications in ventilation systems to regulate volumetric air flows, independent of supply pressure, precise and with very good control characteristic. Types: V51 without reheater, V52 with integrated PWW reheater.


Characteristic features of controllers:

  • Low inherent resistance
  • Low noise level
  • Compact design
  • Suitable for all control functions (variable and constant air volumes)
  • Precise volumetric flow controller insensitive to supply pressure due to 12-point calliper or orifice plate
  • Variant available as duct pressure controller
Questions about the product

Product group

Control Units

Type

Volumetric Flow Controller variable

Article

V51/NS
Pressure Reduction Box

Size/Volumetric flow m3/h (at w = 6 m/s)

  • 100: 170
  • 125: 265
  • 160: 435
  • 180: 550
  • 200: 680
  • 250: 1060
  • 315: 1685
  • 355: 2140
  • 400: 2715

Galvanised steel version (V51 without reheater, V52 with integrated reheater)

Round connecting nozzle with square pressure reduction box (acts as sound attenuator). Casing made of galvanised sheet steel in double walled design with thermal and acoustic insulation. A 4-spoke calliper with 12 measuring points ensures a measurement accuracy of ±5 %. The Barcol-Air damper leaf (double layer with SBR seal in-between) is mounted in low-friction nylon bearings. Shaft material: aluminium. The reheater battery has copper pipe connections (for solder or plug-on connection), each fitted with a drain or vent valve.

Control variants

  • Electronic controllers: Belimo NMV-D3/LMV-D3 in MP, MOD, LON communication, Belimo VRP / VRP-M VFP300 NMQ-SRV-St (V41), Sauter RLE152 / ASV115C, Siemens GLB181.1E/3, Honeywell W7751H3007
  • Pneumatic controllers: Sauter RLP10, Sauter RLP100