Consistently straight
A61/A71 High performance module

A61/A71 high capacity fins constitute a highly efficient radiant ceiling system that ensures the even distribution of heating and cooling energy in a room, creating a pleasant indoor climate. The special geometry of the fins with rounded aluminum profiles ensure freedom from draughts and compliance with standards regarding room air velocity, even at the highest cooling capacity. The fin elements can be arranged as an island or a field on the ceiling.

  • Very high heating and cooling capacity
  • With optional absorbers: Advanced sound absorption values (class B)
  • Powerful and energy efficient
Contact us

Ceiling system

open

Operating principle

Convection

Air supply

visible

Capacity (water)

Cooling (EN 14240:2004):
- up to 140 w/m² (8 K)
Heating (EN 14037:2016):
- up to 137 w/m² (15 K)

Acoustics

Can be combined with sound absorber

Room comfort

Thermal comfort according to
EN ISO 7730, SIA 382/1

Construction

Ceiling system: open

  • Ceiling element with fins

Installation system

  • With threaded rods or ropes

Activation

Water system:

  • Copper tube meander pressed into aluminum profile
  • Copper tube: Ø outer 12 mm

Water

Recommended:
  • Temperature:
    • cooling 16 – 18 °C
    • heating 28 – 37 °C
  • Temperature distance Δt (in-out): 2 – 3 K
  • Pressure drop: 20 – 25 kPa
  • Water flow: 80 – 150 l/h
  • Max. operating pressure: up to 9 bar
  • Water quality: SWKI BT 102-01, BTGA 3.003, VDI 2035

Surrounding

  • Ambient temperatures: +5 – 50 °C
  • Humidity: up to 90 % relative humidity

Capacity

  • Cooling: up to 140 W/m2 (8 K), EN 14240:2004

  • Heating: up to 137 W/m2 (15 K), EN 14037:2016

Supply and exhaust air

Icon_Zu_und_Abluft_RGBweb______

  • Supply and exhaust air elements can be integrated between the elements

Acoustics

  • Can be combined with sound absorber

Integral components

  • Light, fire alarms etc. can be integrated between the elements

Types

Fin type C

  • The single fin is bent sideways left and right

Find type M

  • The single fin is bent sideways left, right and center

Dimensions

  • Installation height: min. 140 mm
  • Standard dimensions:
    • Lenght: 1000 – 3000 mm
    • Width: 390 – 1335 mm
    • Height: 66 mm
  • Special dimensions on request

Material and weight

Material

  • Fins: aluminum
  • Extruded press profiles: aluminum
  • Meander tube: copper
  • Supporting structure: steel

Weight

  • 9 kg/m2 (incl. water)

Versions

Surface

  • Powder coating

Colours

  • Standard RAL 9010
  • Other RAL or NCS colours on request

Fire protections

  • Building material class A2-s1, d0, EN 13501-1